PDFPrintE-mail

Dwyer-Ultra-Sonic Level Transmitter-Usonic

( Dwyer )
Feature:
  •  Two-Wire Loop Powered, HART.
 
  • Easy set-up.
 
  • Automatic Tank Profiling.
 
  • Full Tank Measurement.
 
  • Bench Configuration.
 
  • Level or Open Channel Flow measurements.
 
  • 2-inch Nozzle Mounting.
 
  • User Friendly.
 
  • Ideal for hazardous area installations.
  
Specifications:
Input Power 19 to 30 VDC19 VDC required @ 4 mA minimum. 
Output signal 2-wire, 4-20mA, HART (isolated). 
Maximum Loop Resistance 600 ohms at 24VDC. 
Output Mode Level, Distance, Flow, Volume. 
Display Indications Level,Distance,Flowrate,Totalization,Temperature, Signal Strength, Milliamp User selectable, multiple selections can be scrolled automatically. 
Range 1 to 30 ft. (0.3 to 9.1m). 
Near Zone12 inches (305 mm). 
Minimum Span 3 inches (76 mm). 
Maximum Span 30 ft. (9.1 m). 
Response Time 300 millisecond. 
Accuracy +/- 0.15% or 0.2 inch (5 mm) of sensor range, which ever is  greater. 
Repeatability <0.12 inch (3 mm).