Technical Specifications:

Service

Air and non-combustible, compatible gases.

Wetted Materials

Consult the Tech department

Accuracy

±1% F.S. at 70°F.

Stability

+1% F.S./yr.

Temperature Limits

20 to 120°F (-6.67 to 48.9°C).

Pressure Limits

10 psig (0.69 bar).

Thermal Effect

±0.055% F.S./°F (0.099% F.S./°C).

Power Requirements

10-35 VDC (2 wire).

Output Signal

4 to 20 mA.

Zero and Span Adjustments

Digital push-button zero and span

Loop Resistance

DC: 0-1250 ohms maximum.

Current Consumption

DC: 38 mA maximum.

Electrical Connections

Screw-type terminal block

Display

3.5 digit LCD, 0.7˝ height

Process Connections

1/8˝ I.D. tubing.

Mounting Orientation

Vertical.

Weight

4.8 oz (136 g).