PDFPrintE-mail
Dwyer-Dual-Action Explosion-Proof Pressure Switches-A1niDwyer-Gas Pressure Switches-1996i

Dwyer-Explosion-Proof Differential Pressure Switches-1950i

( Dwyer )
Feature:
  • Model 1950 Explosion-Proof Differential Pressure Switch combines the best features of the popular Dwyer® Series 1900 Pressure Switch with an integral explosion-proof and weatherproof housing, making it an exceptional value for either application. It is CE, UL and CSA listed, FM approved for use in Class I, Div 1, Groups C and D, Class II Groups E, F, and G and Class III hazardous atmospheres (NEMA 7 & 9), Raintight (NEMA 3).
  • Weatherproof features include a drain plug and O-ring seal in cover. Electrical connections are easily made by removing front cover.
  • For convenience the set point adjustment screw is located on the outside of the housing.
  • Twelve models offer set points from .03 to 20˝ w.c. (7.5 to 5 kPa) and from .5 to 50 psi (0.035 to 3.5 bar).
  • The unit is very light and compact — about half the weight and bulk of other explosion-proof or weather-proof switches with separate enclosures.
Specifications:
ServiceAir and non-combustible, compatible gases.
Wetted MaterialsChat with the agent.
Temperature Limits

-40 to 140°F (-40 to 60°C); 0 to 140°F (-17.8 to 60°C) for 1950P-8,

15, 25, and 50. -30 to 130°F (-34.4 to 54.4°C) for 1950-02.

Pressure Limits

Continuous: 1950’s - 45˝ w.c. (0.11 bar);1950P’s - 35 psi (2.41 bar); 1950P-50 only – 70 psi (4.83 bar).

Surge: 1950’s - 10 psi (0.69 bar), 1950P’s - 50 psi (3.45 bar), 1950P-50 only - 90 psi (6.21 bar).

Enclosure RatingIP64, NEMA 3, 7 and 9.
Switch TypeSingle-pole double-throw (SPDT).
Electrical Rating

15 A @, 125, 250, 480 VAC, 60 Hz.

Resistive 1/8 HP @ 125 VAC, 1/4 HP @ 250 VAC, 60 Hz.

Electrical Connections3 screw type, common, normally open and normally closed.
Process Connections1/8˝ female NPT.
Mounting OrientationDiaphragm in vertical position.
Set Point AdjustmentScrew type on top of housing.
Weight3.25 Ib (1.5kg); 1950-02 model, 4.4 lb (2kg).