PDFPrintE-mail
Dwyer-Thermocouple & RTD Limit/Alarm Switch Module-SC12901Love Controls-Digital Temperature Switch Probes-DTSPr

Kimo-Thermostats

( Kimo )

General:

  • Measuring ranges : from 0 to +50°C, from -20 to +80°C, from -50 to +400°C
  • Probes : Pt100 input on terminal block, air tight and ambient
  • ABS housing - IP 65 (Pt100 input on terminal block and air tight models) and IP 30 (ambient model)
  • 5-digit LCD display
  • 1 RCR relay 3A/230 Vac
  • Red LED in front
  • Software or DIP switch configuration
  • Quick and easy mounting with the 1/4 turn system with wall-mount plate.

Specifications:

Temperature

A Pt100 is a resistance with a positive coefficient which

varies according to the temperature. The higher the temperature is, the more the value of the resistance increases.

Temperature Example : for 0°C≈ 100Ω - for100°C≈ 138Ω

Measuring ranges

0 to +50°C (ambient model)

-20 to +80°C (air tight model)

according to the probe : -50 to +400°C

(Pt100 input on terminal block)

Unit of measurement

°C, °F

Accuracy

±1% of reading ±0,4°C

Operating time

1/e (63%) 5 sec. (ambient model)

1/e (63%) 20 sec. (air tight model)

according to probe (Pt100 input on terminal block)

Resolution

0,1°C

Type of transmitter

Pt 100 class A as per DIN IEC 751

Type of fluid

air and neutral gases

Output

1 RCR relay 3A/230 Vac

Relay and alarm status

red LED in front

Set point

1 configurable set point

Power supply

24 V AC/V DC ±10%

Consumption

2 VA

Electromagnetical compatibility

EN 61326

Electrical connection

screw terminal block for cable Ø 1.5 mm² max

Communication to PC

Kimo RS 232 cable

Working temperature

+10 to +40°C (ambient model)

-10 to +50°C (air tight model)

according to probe (Pt100 input on terminal block)

Storage temperature

-10 to +70°C

Environment

air and neutral gases